Servo control

3.5 Torque setpoint limitation

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

73

Fixed and variable torque limit settings

Table 3-1

Fixed and variable torque limit settings

Selection

Torque limitation mode

Mode

Maximum upper or lower torque limits

p1400.4 = 0

Maximum motor or regenerative mode torque

limits p1400.4 = 1

Upper torque limit (as positive

value)

p1520

Motor mode torque limit (as

positive value)

p1520

Fixed torque limit

Lower torque limit (as negative

value)

p1521

Regenerative mode torque limit (as

negative value)

p1521

Upper torque limit

p1522

Motor mode torque limit

p1522

Source for variable torque

limit

Lower torque limit

p1523

Regenerative mode torque limit

p1523

Upper torque limit

p1528

Motor mode torque limit

p1528

Source for variable scaling

factor of torque limit

Lower torque limit

p1529

Regenerative mode torque limit

p1529

Torque offset for torque

limit

Shifts the upper and lower

torque limits together

p1532

Shifts the motor and regenerative

mode torque limits together

p1532

Variants of torque limitation

The following variants are available:
1. No settings entered:

The application does not require any additional restrictions to the torque limits.

2. Fixed limits are required for the torque:

The fixed upper and lower limits or alternatively the fixed motor and regenerative limits

can be specified separately by different sources.

3. Dynamic limits are required for the torque:

– The dynamic upper and lower limit or, alternatively, the dynamic motor and

regenerative limit can be specified separately by different sources.

– Parameters are used to select the source of the current limit.

4. A torque offset can be parameterized.
5. In addition, the power limits can be parameterized separately for motor and regenerative

mode.

NOTICE

Negative values at r1534 or positive values at r1535 represent a minimum torque for the

other torque directions and can cause the drives to rotate if no load torque is generated

to counteract this (see function diagram 5630 in the SINAMICS S List Manual).