Basic information about the drive system

12.10 Rules for wiring with DRIVE-CLiQ

Drive Functions

508

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

– Also change the current controller sampling time and the sampling time of the

inputs/outputs of the DOs not involved so that they again fit into the time grid.

Note
You can call up the "Topology" screen in STARTER to change and/or check the

DRIVE-CLiQ topology for each drive unit.

Note
To enable the function "Automatic configuration" to assign the encoders to the drive,

the recommended rules below must be observed.

Recommended rules

● The DRIVE-CLiQ cable from the Control Unit must be connected to X200 on the first

booksize power section or X400 on the first chassis power section.

● The DRIVE-CLiQ connections between the power sections must each be connected from

interface X201 to X200/from X401 to X400 on the follow-on component.

● A Power Module with the CUA31 should be connected to the end of the DRIVE-CLiQ line.

&8$

&8



;

;

;

;

;

;

;

;

;

;

;

;;

;;

;;

6LQJOH

0RWRU

0RGXOH

;;

;;

;;

6LQJOH

0RWRU

0RGXOH

3RZHU0RGXOH

%ORFNVL]H

'RXEOH

0RWRU

0RGXOH

Figure 12-23 Example: DRIVE-CLiQ line

● The motor encoder must be connected to the associated power unit.

Table 12-14 Connecting the motor encoder via DRIVE-CLiQ

Component

Connecting the motor encoder via DRIVE-CLiQ

Single Motor Module Booksize

X202

Double Motor Module (booksize)

Motor connection X1: Encoder at X202

Motor connection X2: Encoder at X203

Single Motor Module Chassis

X402

Power Module Blocksize

CUA31: Encoder at X202

CU310: Encoder at X100 or via TM31 at X501

Power Module Chassis