Infeed

1.7 Parallel connections of 6-pulse and 12-pulse chassis infeeds

Drive Functions

46

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

1.7

Parallel connections of 6-pulse and 12-pulse chassis infeeds

Description

With Basic Line Modules and chassis units, in addition to 6-pulse parallel infeed (infeed via

two-winding transformer), it is also possible to use a 12-pulse parallel infeed (infeed via

three-winding transformer).
6-pulse parallel infeeds (two-winding transformer)
For the parallel operation of 6-pulse infeeds, a common Control Unit should always be used

for Basic Line Modules and Smart Line Modules.
For Basic Line Modules, a second, separate Control Unit may be used if redundancy is

desired.
12-pulse parallel infeeds (three-winding transformer)
For 12-pulse parallel infeeds via Smart Line Modules, separate Control Units must be

provided for each infeed due to the 30° phase offset between the two converter systems.
Parallel operation of two 12-pulse infeeds, controlled by a single Control Unit, is possible

with Basic Line Modules. If redundancy is desired, a second, separate Control Unit can be

used.
When separate Control Units are used, pre-charging may not be synchronized accurately

enough, i.e. a converter system must be able to pre-charge the total capacity of the drive

line-up. Pre-charging power for the DC link in parallel operation must be dimensioned so that

the capacity of the DC link can be fully charged by a single converter system. Otherwise a

separate pre-charging device must be provided.

L1, L2, L3

L1, L2, L3

0DLQV

0DLQV

,VRODWLQJWUDQVIRUPHU

7UDQVIRUPHUZLWK
VHFRQGDU\ZLQGLQJV
rSKDVHRIIVHW

&RQWURO8QLW

&RQWURO8QLW

&RQWURO8QLW

SXOVHLQIHHG

SXOVHLQIHHG

'5,9(
&/L4

/LQH

0RGXOH

/LQH

0RGXOH

'5,9(&/L4

'&OLQN

'5,9(&/L4

'5,9(&/L4

/LQH

0RGXOH

/LQH

0RGXOH

'&OLQN

/LQHUHDFWRU

/LQHUHDFWRU

/LQHUHDFWRU

/LQHUHDFWRU

Figure 1-11 Parallel infeeds for 6-pulse and 12-pulse operation

Advertising