Communication PROFIBUS DP/PROFINET IO

10.1 Communications according to PROFIdrive

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

357

Bit

Meaning

Comments

BICO

1

No OFF2

Enable possible

OFF2

0

OFF2

Immediate pulse cancellation and power-on

inhibit

BI: p0844

1

Note:

Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.

1

No OFF3

Enable possible

OFF3

0

Emergency stop (OFF3)

Braking with OFF3 ramp p1135, then pulse

cancellation and power-on inhibit.

BI: p0848

2

Note:

Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.

1

Enable operation

Pulse enable possible

3

Enable operation

0

Disable operation

Cancel pulses

BI: p0852

1

Do not reject traversing task

4

Reject traversing task

0

Reject traversing task

BI: p1140

1

No intermediate stop

5

Intermediate stop

0

Intermediate stop

BI: p2640

0/1

Enable setpoint

Activate traversing task

0

No effect

BI: p2631,

p2650

6

Note:

The interconnection p2649 = 0 is also made.

0/1

Acknowledge fault

7

Acknowledge fault

0

No effect

BI: p2103

1

Jog 1 ON

See also the SINAMICS S List Manual, function

diagram 3610

8

Jog 1

0

No effect

BI: p2589

1

Jog 2 ON

See also the SINAMICS S List Manual, function

diagram 3610

9

Jog 2

0

No effect

BI: p2590

1

Control via PLC

This signal must be set so that the process data

transferred via PROFIdrive is accepted and

becomes effective.

Master ctrl by PLC

0

No control via PLC

Process data transferred via PROFIdrive is

rejected - i.e. it is assumed to be zero.

BI: p0854

10

Note:

This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1".

1

Start referencing

11

Start referencing

0

Stop reference

BI: p2595