7.2 Technology controller

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

221

● The D component can be switched to the control deviation or actual value channel.
● The motorized potentiometer of the technology controller is only active when the drive

pulses are enabled.

7.2.3

Commissioning with STARTER

The "technology controller" function module can be activated via the commissioning Wizard

or the drive configuration (configure DDS).
You can check the actual configuration in parameter r0108.16.

7.2.4

Examples

Fill level control

The objective here is to maintain a constant level in the container.
This is carried out by means of a variable-speed pump in conjunction with a sensor for

measuring the level.
The level is determined via an analog input (e.g. AI0 on TB30) and sent to the technology

controller. The level setpoint is defined in a fixed setpoint. The resulting controlled variable is

used as the setpoint for the speed controller.
In this example, terminal board 30 (TB30) is used.

;DFW

6HQVRU

Figure 7-1

Liquid level control: application