6.4 Sinusoidal filter
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
185
CAUTION
If a drive in a Safety Integrated line-up is deactivated via p0105, r9774 is not read
correctly because the signals from the deactivated drive are no longer updated.
Remedy: Remove this drive from the group before you deactivate it. See also: Function
Manual (FH1), chapter Safety Integrated
Overview of key parameters (see SINAMICS S List Manual)
● p0105 Activate/deactivate drive object
● r0106 Drive object active/inactive
● p0125 Activate/de-activate power unit component
● r0126 Power unit component active/inactive
● p0145 Activate/deactivate encoder interface
● r0146 Encoder interface active/inactive
● p9495 BICO response to de-activated drive objects
● p9496 Re-establish BICO to the now activated drive objects
● r9498[0 ... 29] BICO BI/CI parameter to de-activated drive objects
● r9499[0 ... 29] BICO BO/CO parameter to de-activated drive objects
6.4
Sinusoidal filter
Description
The sinusoidal filter limits the rate of rise of voltage and the capacitive charge/discharge
currents that usually occur with inverter operation. They also prevent additional noise caused
by the pulse frequency. The service life of the motor is the same as that with direct line
operation.
CAUTION
If a sinusoidal filter is connected to the converter, the converter must be activated during
commissioning to prevent the filter from being destroyed.
Usage restrictions for sinusoidal filters
The following restrictions must be taken into account when a sinusoidal filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● The modulation type is permanently set to space vector modulation without
overmodulation. This reduces the maximum output voltage to approx. 85 % of the rated
output voltage.