Servo control

3.11 Sensorless operation (without an encoder)

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

89

Since the dynamic response in operation without an encoder is lower than in operation with

an encoder, accelerating torque pre-control is implemented to improve the control dynamic

performance. It controls, knowing the drive torque, and taking into account the existing

torque and current limits as well as the load moment of inertia (motor moment of inertia:

p0341*p0342 + load torque: p1498) the required torque for a demanded speed dynamic

performance optimized from a time perspective.

Note
If the motor is operated with and without an encoder (e.g. p0491 not 0 or p1404 < p1082),

the maximum current during operation without an encoder can be reduced via p0642

(reference value is p0640) in order to minimize interfering, saturation-related motor data

changes during operation without an encoder.

A torque smoothing time can be parameterized via p1517 for the torque pre-control. The

speed controller needs to be optimized for operation without an encoder due to the lower

dynamic response. This can be carried out via p1470 (P gain) and p1472 (integral time).
In the low-speed range, the actual speed value, the orientation, and the actual flux can no

longer be calculated during operation without an encoder due to the accuracy of the

measured values and the parameter sensitivity of the technique. For this reason, an open-

loop current/frequency control is selected. The switchover threshold is parameterized via

p1755 and the hysteresis via p1756.
To accept a high load torque even in the open-loop controlled range, the motor current can

be increased via p1612. To do so, the drive torque (e.g. friction torque) must be known or

estimated. An additional reserve of approx. 20% should also be added. In synchronous

motors, the torque is converted to the current via the motor torque constant (p0316). In the

lower speed range, the required current cannot be measured directly on the Motor Module.

The default setting is 50% (synchronous motor) or 80% (induction motor) of the rated motor

current (p0305). When parameterizing the motor current (p1612), you must take into account

the thermal motor load.

Note
Sensorless operation (without an encoder) is not permitted for vertical axes or similar.

Sensorless operation is not suitable for a higher-level closed-loop position control either.

The start behavior of synchronous motors from standstill can be improved further by

parameterizing the pole position identification (p1982 = 1).

Behavior once pulses have been canceled

Once the pulses have been canceled in operation without an encoder, the current actual

speed value of the motor can no longer be calculated. Once the pulses are enabled again,

the system must search for the actual speed value.
p1400.11 can be used to parameterize whether the search is to begin with the speed

setpoint (p1400.11 = 1) or with speed = 0.0 (p1400.11 = 0). Under normal circumstances,

p1400.11 = 0 because the motor is usually started from standstill. If the motor is rotating

faster than the changeover speed p1755 when the pulses are enabled, p1400.11 = 1 must

be set.
If the motor is rotating and the start value for the search is as of the setpoint (p1400.11 = 1),

the speed setpoint must be in the same direction as the actual speed before the pulses can