Applications

11.1 Parallel operation of communication interfaces for CU320

Drive Functions

452

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

Properties of the cyclic interfaces IF1 and IF2
The following table shows the different features of the two cyclic interfaces:

Table 11-1 Properties of the cyclic interfaces IF1 and IF2

Feature

IF1

IF2

Setpoint (BICO signal source)

r2050, r2060

r8850, r8860

Actual value (BICO signal sink)

p2051, p2061

p8851, p8861

PROFIdrive conformance

Yes

No

PROFIdrive telegram selection (p922)

Yes

No

Isochronous mode possible

Yes

No

Slave-to-slave communication (PROFIBUS only)

Yes

Yes

List of drive objects (p978)

Yes

Yes

Max. PZD (16bit) setpoint / actual value SERVO

16 / 19

16 / 16

Max. PZD (16bit) setpoint / actual value vector

32 / 32

16 / 16

Max. PZD (16bit) setpoint / actual value infeeds

5 / 8

5 / 8

Max. PZD (16bit) setpoint / actual value TM41

16 / 19

Max. PZD (16bit) setpoint / actual value TM15

30 / 30

Max. PZD (16bit) setpoint / actual value TM17

36 / 36

Max. PZD (16bit) setpoint / actual value TM / TB (other)

5 / 5

Max. PZD (16bit) setpoint / actual value CU (device)

5 / 15

Table 11-2 Implicit assignment of hardware to cyclic interfaces

Plugged hardware interface

IF1

IF2

No option, onboard interface only (PROFIBUS)

Onboard

--

PROFINET option (CBE20)

COMM board

--

CAN option (CBC10)

Onboard

COMM board

PROFIBUS option

Onboard

--


For parallel operation of the hardware interfaces and the explicit assignment to the cyclic

interfaces IF1 and IF2, the new parameter p8839[0,1] "PZD Interface hardware assignment"

exists for the device IO in the expert list.
The default setting of p8839[0,1]=99 enables the implicit assignment (see table above).
An alarm is generated in case of unvalid or inconsistent parameterization of the assignment.

Note
Parallel operation of PROFIBUS and PROFINET
Isochronous applications can only run via the cyclic interface IF1. With an additional

PROFINET module plugged in, there are two parameterization options:
- p8839(0) = 1 and p8839(1) = 2: PROFIBUS isochronous, PROFINET cyclic
- p8839(0) = 2 and p8839(1) = 1: PROFINET isochronous, PROFIBUS cyclic