Configuring Notifications

Enter the monitoring end

Enter the Minimum amount of feed-in power

Enter the Deviation as a percentage

Enter the fault duration in intervals

This indicates how long a fault should be continuously present, before it is recognized as a fault. The

minimum fault duration is 5 minutes, but a longer one should be selected.

An interval corresponds to 5 minutes. The fault duration is determined by the number of intervals en-

tered and display under the input box.

Enter the Maximum number of message to be sent per day

So that malfunctions are not reported too often, a maximum number of messages per day can be

defined.

Maximum number of messages per day

Snow cover

False messages may occur if the unit is covered in snow. These are messages from the power compari-

son that occur if modules are partially covered, or failure messages if the inverter is no longer switched

on because it is fully covered by snow.

There are two ways to minimize this problem:

The minimum percentage value above which power monitoring starts should be set as high as possi-

ble, e.g. 30%. For example, if the generator power is 4500 Wp, power monitoring will start only at 1350

watts. The partly shaded modules reduce the power from the unshaded modules so that the required

1350 watts is rarely or never reached. This is how the problem of partial covering is resolved.

Failure messages are always sent when the inverter is not working or when it is not online at times that

have been configured as unshaded. It is then assumed that there is a fault. Complete snow covering

would therefore be reported as a failure. To solve this problem, check the box for snow coverage. If

the box is checked, no failure message is sent if all of the inverters are offline. This is not taken into

account in the period from 01 November to 30 April. Outside of this period, the snow covering func-

tion is automatically disabled. Monitoring then works as usual and also reports complete failures of all

of the inverters.

Note

For PV plants with only one inverter, an inverter failure notification is sent even when the

snow cover parameter is active.

Select

Message as

Activate required options and enter values.

SAVE

settings

.

In the Save menu, there are three different options:

SAVE

SAVE MULTIPLE

SAVE ALL

Save

When using this button, the settings for the device selected as the device are saved.

Save multiple