Solare Datensysteme Solar-Log User Manual

Page 146

Advertising
background image

146

Special functions

versions can be configured.

Ripple control receivers generally possess 2 to 5 relays. The assignment of the individual relay states for a

particular shift factor is specified by the respective grid operator and stored in the Solar-Log™ using this

matrix. In this way the connected inverters can be adjusted to meet the specified reduction levels.

Fig.: Channel settings for remote controlled cos (Phi)

For each level, the input signal combination and a value for the shift factor in cos (Phi) is entered.

Checking the box next to the digital inputs of the PM+ interface (D_IN_1 to D_IN_4) means that the input is

supplied with 5V from pin 6 to reduce the output on the cos phi defined in the box "cos (Phi)".

Four levels are shown in the basic setting. The "+" sign can be used to extend the list by additional levels.

Procedure:

Select

remote controlled.

Select the

interface

of the inverter that is to be reduced.

Enter the channel settings for power reduction

according to the specifications and wiring

.

Select options.

SAVE settings.

More Options.

Switching from the remote-controlled cos (Phi) to the possible characteristic curves can be implemented

via assigned combinations of signals to the PM+ interface.

Fig.: Switching to reactive power characteristic curves with certain signals

If a switch to the characteristic curve operating mode (P/Pn and Q(U)) is required due to a certain ripple

control receiver signal, the respective levels for the switch can be entered in the input box. If no switch

should take place, enter 0 in the input box.