Connector Assignments and Wiring

10�6 PM+

The Solar-Log™ PM+ models come with a 6-pin PM+ interface on the top side of the Solar-Log

TM

.

The interface has been designed to link the ripple control receivers or telecontrol plants with potential-free

signal contacts. Up to two ripple control receivers can be connected. This allows the commands from grid

operators for active and reactive power to be interpreted.

Fig.: 6-pin PM+ interface

Fig.: 6-pin Terminal block connector

PM+

PIN

Assignment

Description

1

+5V

Control voltage for active
power control

2

D_IN_1

Control input 1

3

D_In_2

Control input 2

4

D_In_3

Control input 3

5

D_In_4

Control input 4

6

+5V

Control voltage for reactive
power reduction

To provide the highest possible flexibility, the individual active and reactive power values can be assigned

to inputs D_IN_1 to D_IN_4

See Chapter

“Feed-In Management“ 90 130

for more information

See the appendix for more ripple control receiver connection examples