233

Appendix

32�4�4 Variation with 5 relays (including emergency stop)

Specifications

Ripple control receiver signals

Level

K1

K2

K3

K4

K5

Power

1

On

Off

Off

Off

Off

100%

2

Off

On

Off

Off

Off

60%

3

Off

Off

On

Off

Off

30%

4

Off

Off

Off

On

Off

0%

5

On

Emergency
stop

The relay is continuously activated for a particular level (condition). There is always only one relay that is

activated.

Wiring

Fig.: Wiring a ripple control receive with 3 relays - example 3

Fig.: Wiring a ripple control receive with 5 relays - example 4

WARNING

Emergency stop commands may not be processed via the Solar-Log™ These com-

mands have to function directly with the corresponding protection equipment such as

grid and plant protection, section switches and Q/U protection.