Special functions

23�2�9 Adjustable Reduction with the Calculation of Self-Consumption

This function allows the maximum amount of grid feed-in power to be configured. The reduction level

in regard to the amount of connected generator power can be freely defined as a percentage (X%). The

amount of self-consumption is taken into account for this calculation. The Solar-Log™ only regulates the

inverters when the amount of feed-in power for the grid has reached the limit. If there is enough self-con-

sumption, the inverters continue to operate without any reductions.

Procedure:

Select

Adjustable reduction with the calculation of self-consumption

Enter

the

percentage

for the adjustable reduction.

Select the

interface

of the inverter that is to be reduced.

SAVE

settings.

Note

The Solar-Log™ needs to be linked to a consumption meter to implement this function.

Please note the instructions in chapter”12.5 External power meter”.

23�3 Reactive Power

The following modes are available from the

Special Functions | Feed-in Management | Reactive power

menu:

Deactivated

fixed value cos (Phi) shift factor

fixed reactive power in Var

variable cos (Phi) shift factor over characteristic curve P/Pn

variable reactive power over characteristic curve Q(U) (only Solar-Log 2000 PM+ with Utility Me-
ter)

Remote controlled fixed value cos (Phi) shift factor(only Solar-Log™ PM+)

Note

The active power reduction mode that needs to be implemented for a particular PV plant

is determined by the national laws and guidelines.

The planner and/or installer of your plant or the respective grid operator can provide

you with information regarding the method of reactive power control.

Note

The feed-in management function is not available for all supported inverters. Prior to

installation please check whether PM+ is supported by the inverters used.

Additional information as well as our inverter database can be found under

www.so-

lar-log.com/pm+

.