Solare Datensysteme Solar-Log User Manual

Page 134

Advertising
background image

134

Special functions

Channel settings for power reduction section

The relay outputs for the ripple control receiver are connected to the PM+ input of the Solar-Log™ PM+.

This allows the grid operator's signals to be evaluated by the Solar-Log™.

Fig.: Schematic diagram of a ripple control receiver with four relays.

The relay for active power control is wired to the PM+ interface.

Note

The function of the PM+ interface is only possible when the contacts of the

ripple control receiver are potential free and are wired with a supply voltage of

5VDC from the PM+ interface.

In practice, various ripple control receivers with varying numbers of relays and different signal codes are

used. The configuration matrix for the Solar-Log™ PM+ thus offers maximum flexibility – most common

versions can be configured.

Ripple control receivers generally possess 2 to 5 relays. The assignment of the individual relay states for

certain reduction levels is specified by the respective network operator and stored in the Solar Log™ using

this matrix. In this way the connected inverters can be adjusted to meet the specified reduction levels.

Fig.: Channel settings for power reduction