23�2�5 Remote controlled active power reduction with the calculation of self-

consumption (only Solar-Log™ PM+)

This function is an enhancement to the

Remote controlled active power reduction

function described in

the previous chapter. This function does not correspond to provisions of the German EEG laws and has to

be arranged with the grid operator before being used.

Note

The Solar-Log PM+ needs to be

linked to a consumption meter to implement this function. Please note the instructions in

chapter”12.5 External power meter”.

The configuration of this corresponds to that already described for the remote controlled active power

reduction.

The instruction for integrating the meters into the electric wiring of the house or building are found in the

appendix.

Note

Self-consumption is taken into account with a command (less than 100% and greater

than 0%). The inverter(s) supply a higher output than the command value by taking the

current consumption into account.

Self-consumption is not taken into account with the 0% command value. As a safeguard

here, the plant is always limited to 0%.

23�2�6 70% fixed reduction

By activating this menu item the inverter(s) are controlled to be fixed at 70% of the installed DC power.

Enter the

Maximum AC Power

and

Connected Generator Power

as reference values in the

Configura-

tion | Basic | Inverter

menu.

The maximum power output for the inverters can be calculated from the connected generator power value

that has been entered.

Procedure

Select 70%

fixed reduction

.

Select the

interface

of the inverter that is to be reduced.

SAVE

settings

.

Note

Changes to the

Maximum AC Power

of the inverter in

Configuration | Basic | Inverter

menu are disabled.

Enter your password via the Log-on as Installer / PM to enable changes.