Solare Datensysteme Solar-Log User Manual

Page 144

Advertising
background image

144

Special functions

SAVE

settings.

The characteristic curve displayed changes according to the values entered.

4-point characteristic curve

By selecting "4-point characteristic curve" it is possible to define a characteristic curve using four points.

Procedure:

Select

variable reactive power via the characteristic curve Q(U)

as the type.

Activate the

interfaces

.

Select

4-point characteristic curve

.

Define

the

characteristic curve points A, B, C and D

based on the boxes U/Uc, Q/SAmax and put a

check in front of inductive/under-excited.

SAVE

settings.

The characteristic curve displayed changes according to the values entered.

Reductions

The following configuration options are available in the Reductions section.

Gradient limit (adjustment rate):
If the power company requires a reduction, it has to be configured in this box. (Enter the values in
seconds)

Max. cos(phi) inductive/underexcited and max. cos(phi) capacitive/over-excited:
A maximum shift factor can be defined wit this the reduction. With this, it can be that less reactive
power is fed-in into the grid than what the characteristic curve allows in the partial load range in
order to maintain the shift factor limits.

Note

Entering zero as the value deactivates the particular limit.

Advertising