226

Appendix

32�4 Connection examples for ripple control receivers

Grid operators have not agreed on a universal standard for ripple control receiver signals. As result, there

are several variations with the respective wiring and configuration in the Solar-Log™ firmware.

All of the examples refer to active power reduction. When ripple control receivers are used for reactive

power, they are configured in the same way.

Note

The following connection examples are require-

ments from different grid operators. The labels for

the relays in the wiring diagram and in the So-

lar-Log™'s configuration matrix can differ.

WARNING

Please note the specifications for the load of the

ripple control receiver's relays. In certain circum-

stances, the relays have to be connected to inter-

mediate relays.

In any case, the inputs D_IN_X have to be supplied

with the control voltage (5V DC) from the So-

lar-Log™ (PM+ interface Pin 1 and 6).

WARNING

When connecting two ripple control receivers: If

the ripple control receiver uses binary signal cod-

ing, signal feedback via the ripple control receiver

for the reactive power must be prevented by fitting

diodes.

WARNING

Emergency stop commands may not be

processed via the Solar-Log™ These commands

have to function directly with the corresponding

protection equipment such as grid and plant pro-

tection, section switches and Q/U protection.