Special functions

23�3�4 Variable cos (Phi) shift factor over characteristic curve P/Pn

The function allows the cos (Phi) to be adjusted according to characteristic curve P/Pn.

With a characteristic curve P/Pn, the ratio of the currently generated power (P) to nominal power (maxi-

mum output) (Pn) is determined. A Cos (Phi) is assigned to ratio by a characteristic curve.

The function is also referred to as Phi (P).

The currently generated power (P) is calculated by the Solar-Log™ based on the inverter data. If an Utility

Meter with power measurement is available, the output value will be used instead.

Note

Please check that all of the Solar-Logs in a master/slave setup have the same firmware

version, especially for the characteristic curve P/Pn with the Utility Meter.

Type of characteristic curve section

Using this menu item a characteristic curve specified by the grid operator can be stored. In principle a dis-

tinction is made here between a 2-point and a 4-point characteristic curve.

2-point characteristic curve

By selecting "2-point characteristic curve" it is possible to define a characteristic curve using two points.

Procedure

Select

Variable cos (Phi) shift factor over characteristic curve P/Pn

from the menu.

Activate

Interfaces

.

Select

2-point characteristic curve

.

Define

the

characteristic curve points A and B

based on the boxes P/Pn and cos (Phi) and put a

check in front of "inductive."

SAVE

settings.

The characteristic curve displayed changes according to the values entered.

4-point characteristic curve

By selecting "4-point characteristic curve" it is possible to define a characteristic curve using four points.

Procedure

Select

Variable cos (Phi) shift factor over characteristic curve P/Pn

from the menu.

Activate

Interfaces

.

Select

4-point characteristic curve

.

Define

the

characteristic curve points A, B, C and D

based on the boxes P/Pn, cos (Phi) and put a

check in front of inductive/under-excited.

SAVE

settings.

The characteristic curve displayed changes according to the values entered.