4 lockout feature, 4 lockout – Honeywell UDC2500 User Manual

Page 105

Advertising
background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

91

Table 4-1 Procedure to Enter a Security Code

Step

Operation

Press

Result

1

Enter Set Up

Mode

Setup

Setup

Upper Display = SET UP

Lower Display = TUNING

2

Select any Set

Up Group

Function

Function

Function

Upper Display = 0

Lower Display = SECUR

3

Security Code

Entry

or

To enter a four digit number in the upper display

(0001 to 9999)

This will be your security code.

4.4 Lockout Feature

Introduction

The lockout feature in the UDC2500 is used to inhibit changes (via keyboard) of certain
functions or parameters by unauthorized personnel.

Lockout levels

There are different levels of Lockout depending on the level of security required. These
levels are:

NONE

No Lockout. All groups Read/Write.

CAL

Calibration prompts are deleted from the Setup List.

CONF

Timer, Tuning, SP Ramp, and Accutune are Read/Write. All other Setup

groups are Read only. Calibration Group is not available.

VIEW

Timer, Tuning, and SP Ramp are Read/Write. No other parameters are

available.

ALL

Timer, Tuning, and SP Ramp are Read only. No other parameters are

viewable.

See Subsection 3.4 - Tuning Parameters Set Up Group prompts to select one of the
above.

Security Code (see Subsection 4.3)