12 display – Honeywell UDC2500 User Manual

Page 231

Advertising
background image

Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

217

10.7.12 Display

Table 10-20 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Display.

Table 10-20 Set-up Group – Display

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Decimal Point
Location

009B 155

INT R/W

0 = XXXX – Fixed
1 = XXX.X – Floating

decimal point to one

2 = XX.XX – Floating

decimal point to two

Temperature
Units

0081 129

INT R/W

0 = °F

1 = °C
2 = None

Power
Frequency

00A6

166

INT

R/W

0 = 60 Hertz

1 = 50 Hertz

Language
(Displays)

00C0

192

INT

R/W

0 = English

1 = French
2 = German
3 = Spanish
4 = Italian
5 = Numeric

Lower Display
Enable

00AE

174

INT

R/W

0 = Enable

1 = Disable

Lower Display

00AF

175

INT

R/W

0 = Setpoint

1 = PRY – PV with Label
2 = PRN – PV witout Label

TC Diagnostics 009f

159

INT

R/W

0 = Enable
1 = Disable

Advertising