Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

45

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

DIS

DISABLE – The current SetPoint is used to
derive a single set of blended tuning
parameters. This tuning is performed over
the range of the output limits similar to
Simplex Tuning. The Tuning Parameters
derived are placed into both the HEAT and
COOL tune sets (PID 1 and PID 2).

AT ERR
(Read Only)

304

ACCUTUNE ERROR STATUS—When an
error is detected in the Accutune process, an
error prompt will appear

NONE 0

NONE—No errors occurred during last
Accutune procedure.

RUN 5

RUNNING—An Accutune process is still
active checking process gain, even though
“TUNE” is not lit. It does not affect keyboard
operation.

ABRT 4

CURRENT ACCUTUNE PROCESS
ABORTED
—Caused by one of the following
conditions:
• changing to manual mode
• digital input detected
• in heat region of output but a cool output
was calculated, or vice versa.

SP2 6

SP2—LSP2 not configured or a Setpoint
other than LSP1 or LSP2 is in use.