Modbus RTU Function Codes

182

UDC2500 Universal Digital Controller Product Manual

4/07

9.3 Function Code 20 (14h) - Read Configuration Reference Data

Description

Function code 20 (14 Hex) is used in this instrument to read information stored in its
configuration database. Each configuration item is explicitly addressed by a file number
and register address. IEEE 32-bit floating point and 16-bit integer formats are supported.

Request and Response Formats

The Request and Response formats for Function code 20 (14 Hex) are shown below.
Details for each block reference follow.

Request Message Format

Slave

Address

Byte

Count

Reference

Type

Function
Code 14

Reference

Type

File

Number

Register

Count

Register
Address

Reference

Type

File

Number

Register

Count

Register
Address

CRC
Data

CRC
Data

Response Message Format

Slave

Address

Byte

Count

Reference

Type

Function
Code 14

Reference

Type

Data

Reference

Type

Data

Byte

Count

Data

Data

Data

Data

Byte

Count

Data

Data

Data

Data

CRC
Data

CRC
Data

Byte Count

The Byte Count equals the number of bytes transmitted in either the request or response
message and will be the minimum number required to transmit all requested data.

Data Byte Count

The Data Byte Count is the number of data bytes of the sub response including the
Reference Type but not including itself. A floating point sub response has four bytes of
data and one byte representing the reference type making the data byte count equal to
five.