Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

53

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

50

CURRENT DUPLEX RANGE (SPLIT)—This
setting should be used for Relay/Current and
Current/Relay Duplex Outputs. It can also be
used for Current Duplex when an Auxiliary
Output board is present. This enables the
normal control current output to provide heat
control and the auxiliary current output to
provide cool control. To enable this:

• AUX OUT in the Options Set Up group

must be selected for Output.

• The Auxiliary Current Output is scaled as

desired for 0-50 % controller output.

• Deadband for this configuration only

applies to the Current Output. The
Auxiliary Output must have the Deadband
scaled in.

FOR EXAMPLE:

If a 2 % Deadband is desired, then enter 2.0
for the Deadband selection in the Control
Algorithm group. This will apply Deadband to
the Current Output. In the Options group, set
the Auxiliary Output LOW VAL selection to
49.0 and the HIGH VAL selection to 0.0.

100

CURRENT DUPLEX RANGE (FULL)
enables the Current Output to provide both
heat and cool functions for control over 0-
100 % of the controller output. The PID heat
parameters apply when the output is greater
than 50 % and the PID cool parameters
apply when the output is less than 50 %. The
second current output is not required for this
type of duplex operation.