Input Calibration

4/07

UDC2500 Universal Digital Controller Product Manual

143

0 to 10 Volts

Refer to Figure 5-6 and wire the controller according to the procedure given in Table 5-8.

Table 5-8 Set Up Wiring Procedure for 0 to 10 Volts

Step

Action

1

Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-6.

2

Place voltage source at zero before switching on.

3

Do not switch voltage source ON/OFF while connected to the instrument.

Volt

Source

_

+

1

2

3

100K pair

26+
27-

Volt

Source

_

+

1

2

3

100K pair

26+
27-

Figure 5-6 Wiring Connections for 0 to 10 Volts

Milliamperes

Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-7.

Table 5-9 Set Up Wiring Procedure for Milliampere Inputs

Step

Action

1

Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-7.

2

Place current source at zero before switching on.

3

Do not switch current source ON/OFF while connected to the instrument.

Milliampere

Source

26+

27-

+

_

250 ohms

Milliampere

Source

26+

27-

+

_

250 ohms

Figure 5-7 Wiring Connections for 0 to 20 mA or 4 to 20 mA Inputs