Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

193

10.5 Setpoints

Overview

You can use two separate local setpoints in the controller. The identifying register
addresses listed in Table 10-5 allow you to select which setpoint you want to use and to
enter a value in Engineering Units (whichever is selected at register address 00A1) for
that setpoint via communications.

Register Addresses

Make your selection using register address 00AD and enter the value for the setpoint
chosen using register address in Table 10-5.

Table 10-5 Setpoint Code Selections

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Local Setpoint #1

0027

039

FP

R/W

Value within the setpoint
range limits

Local Setpoint #2

0035

053

FP

R/W

Value within the setpoint
range limits

Number of Local
Setpoints

00AD 173

INT

R/W

00 = Local Setpoint #1
only

01 = 2nd Local Setpoint via
keyboard or
communications

Associated Parameters

Refer to Table 10-6 to display or change any of the parameters associated with the
setpoint.

Table 10-6 Setpoint Associated Parameters

Parameter

Register Address

Hex

Decimal

Setpoint Limits

0007, 0008

007, 008

Computer Setpoint

007D

125