Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

203

10.7.5 Output

Algorithms

Table 10-13 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Output.

Table 10-13 Set-up Group – Output

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Output
Algorithm

00A0

160

INT

R/W

0 = Time Simplex
1 = Not Used
2 = Current Simplex
3 = Three Position Step or

Position Proportioning

4 = Time Duplex
5 = Current Duplex
6 = Current/Time Duplex
7 = Time/Current Duplex

Relay Cycle
Time
Increments

00BE 190

INT

R/W

0 = 1 second increments
1 = 1/3 second increments

Motor Time for
Three Position
Step

004B

075

INT

R/W

5 to 1800 seconds

Current Range
for Current
Duplex

0099 153

INT R/W

0 = Full (100%)
1 = Split (50%)

Current Output
Range

00EA 235

INT R/W

0 = 4-20 mA
1 = 0-20 mA