Troubleshooting/Service

4/07

UDC2500 Universal Digital Controller Product Manual

169

Procedure #5

Table 7-9 explains how to troubleshoot Current/Time or Time/Current Proportional
Output failure.

Table 7-9 Troubleshooting Current/Time or Time/Current Proportional

Output Failure

Step

What to do

How to do it

1

Make sure the controller is configured
for Time/Current or Current/Time
Proportional output.

Make Output Algorithm Set Up group function
prompt OUT ALG = TCUR or CURT.

Refer to Section 3 – Configuration.

2

Check the field wiring.

Make sure the NO or NC contact wiring selection
is correct.

Refer to Section 2 - Installation for details.

3

Check the relay output.

Put the controller into Manual mode. Vary the
output above and below the present value.
Observe OUT1 indicator on the operator interface.
Listen for a click from the relay when the OUT1
indicator changes state.

4

Check the Current Proportional
Output.

Put the controller into Manual mode and change
the output from 0 % to 100 % (4-20 mA). Use a DC
milliammeter at the rear terminals to verify the
output.

5

Recalibrate the controller.

Refer to Section 6 - Output Calibration for details.

6

Change relay and/or Current Output
boards.

Installation instructions supplied with new board.