Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

83

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

FREQ 1203

60
50

0
1

POWER LINE FREQUENCY—Select
whether your controller is operating at 50 or
60 Hertz.

ATTENTION For controllers powered by
+24 Vdc, this configuration should be set to
the AC line frequency used to produce the
+24 Vdc supply.

Incorrect setting of this parameter may cause
normal mode noise problems in the input
readings.

DISPLY 1205


SP
PRY

PRN

0
1

2

DEFAULT DISPLAY—For single display
units, only. This setting selects the default
parameter shown on the upper display.
Pressing the LOWER DISPLAY key will
cycle through all applicable values. One
minute after the last press of the display key,
the display will revert to the display
configured here.

SETPOINT—Active Setpoint
PV-YES
—Process Variable with lower
display prompt.
PV-NO
—Process Variable with no lower
display prompt.

LWRDSP 1204

ENAB
DIS

0
1

LOWER DISPLY—For dual display units,
only. Select whether the unit uses single or
dual display.

ENAB—Enable Dual Display
DIS—Disable Dual Display (Single Display
Only)

LNGUAG 1206

ENGL
FREN
GERM
SPAN
ITAL
NUMB

0
1
2
3
4
5

LANGUAGE—This selection designates the
prompt language.

ENGLISH
FRENCH
GERMAN
SPANISH
ITALIAN
NUMERIC

TCDIAG 1207

ENAB
DIS


0
1

THERMOCOUPLE DIAGNOSTICS—Enable
or disable Thermocouple diagnostic
messages.

ENAB—Enable Diagnostic Messages
DIS—Disable Diagnostic Messages