Honeywell UDC2500 User Manual

Page 156

Advertising
background image

Input Calibration

142

UDC2500 Universal Digital Controller Product Manual

4/07

Radiamatic, Millivolts, Volts or Thermocouple Differential Inputs

Refer to Figure 5-5 and wire the controller according to the procedure given in Table 5-7.

Table 5-7 Set Up Wiring Procedure for Radiamatic, Millivolts, Volts or

Thermocouple Differential Inputs (Except 0-10 Volts)

Step

Action

1

Connect the copper leads from the calibrator to the Input #1 terminals as shown in
Figure 5-5.

2

Place current/voltage source at zero before switching on.

3

Do not switch current/voltage source ON/OFF while connected to the instrument.

ATTENTION

For Radiamatic inputs only, set Emissivity value to 1.0. See Subsection 3.9 – Configuration Set
Up prompt INPUT1, function prompt EMISS.

Millivolt or
Volt Source

26+

27-

+

_

Millivolt or
Volt Source

26+

27-

+

_

Figure 5-5 Wiring Connections for Radiamatic, Thermocouple Differential,

Millivolts or Volts (Except 0 to 10 Volts)