6 error codes – Honeywell UDC2500 User Manual

Page 123

Advertising
background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

109

4.11.6 Error

Codes

Table 4-16 Procedure for Accessing Accutune Error Codes

Step

Operation

Press

Result

1

Select Accutune

Set-up Group

Setup

Setup

Upper Display = SET

Lower Display = ATUNE

2

Go to Error Code

Prompt

Function

Function

Function

Upper Display = (an error code)
Lower Display = ATERR
Table 4-17 lists all the error codes, definitions, and
fixes.

Table 4-17 Accutune Error Codes

Error Code

(Upper Display)

Definition

Fix

RUN

ACCUTUNE RUNNING

The Accutune process is still active (Read Only)

NONE

NO ERRORS OCCURRED
DURING LAST ACCUTUNE
PROCEDURE

None

IDFL

PROCESS IDENTIFICATION
FAILURE
Autotune has aborted
because an illegal value of
GAIN, RATE, or reset was
calculated.

• Illegal

Values

– try Accutune again.

• untunable process -- contact local application

engineer.

ABRT

CURRENT ACCUTUNE
PROCESS ABORTED
caused by the following
conditions:
a. Operator changed to
Manual mode
b. Digital Input detected
c. In Heat region of output
and a Cool output calculated
or vice versa.

Try Accutune again

SP2

LSP2 not enabled or LSP1 or
LSP2 not in use (only applies
to Duplex Tuning)

Enable LSP2 and configure the desired LSP1 and
LSP2 setpoints.

Aborting Accutune

To abort Accutune and return to the last previous operation (SP or output level), press

M-A/RESET

key to abort the Accutune process.