Troubleshooting/Service

4/07

UDC2500 Universal Digital Controller Product Manual

173

Procedure #9

Table 7-13 explains how to troubleshoot a Communications failure

Table 7-13 Troubleshooting an Ethernet Communications Failure

Step

What to do

How to do it

1

Check the IP address, Subnet
Mask address and Gateway
address settings.

See the PIE Tool Manual.

2

Check if the Ethernet Connection
is active.

Looking into the instrument, there should be steady
green LED. If this is not present, then the
instrument is not seeing a valid Ethernet
connection. See Section 2.7 for wiring diagrams. A
second green LED will blink during actual Ethernet
transactions.

3

Change Ethernet
Communications board.

Installation instructions provided with new
board.

4

Change Controller

Procedure #10

Table 7-14 explains how to troubleshoot Auxiliary Proportional Output failure
symptoms.

Table 7-14 Troubleshooting Auxiliary Output Failure

Step

What to do

How to do it

1

Make sure the controller is
configured for Auxiliary Output
and the proper range (4 to 20 or
0 to 20) is configured.

Make Options Set Up group function prompt
AUX OUT any selection other than NONE. If
this prompt does not show up, check if DIG IN
2 is enabled. If so, then as Auxiliary Ouptut
and Digital Input 2 are mutually exclusive, you
must chose which one of these features you
wish to use.

Make the Options Set UP group function
prompt CRANGE = 4–20 or 0–20 per your
application.

Refer to Section 3 - Configuration.

2

Check the field wiring.

Output impedance must be less than or equal
to 1000 ohms.

3

Check the output.

Change the AUX OUT selection to OUTPUT.
Put the controller into Manual mode and
change the output from 0 % to 100 % (4-20
mA). Use a DC milliammeter at the rear
terminals to verify the output.

4

Recalibrate the Auxiliary output. Refer to Section 6 - Output Calibration for

details.

5

Change Auxiliary Output board.

Installation instructions provided with new
board.

6

Change Controller