Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

101

4.8.2 What happens when you change modes

Table 4-8 Changing Control Modes (Dual Display Only)

Control Mode

Definition

Manual to
Automatic Local
Setpoint

The Local Setpoint is usually the value previously stored as the Local Setpoint.
PV tracking is a configurable feature which modifies this. For this configuration,
when the controller is in manual mode, the local setpoint value tracks the process
variable value continuously.

Manual or Auto
Local to Automatic
Remote SP

The Remote Setpoint uses the stored ratio and bias to calculate the control
setpoint.

Automatic Remote
Setpoint to Manual
or Auto Local
Setpoint

If configured for local setpoint tracking, RSP, when the controller transfers out of
remote setpoint the last value of the remote setpoint is inserted into the local
setpoint.
If LSP tracking is not configured, the local setpoint will not be altered when the
transfer is made.

4.9 Setpoints

Introduction

You can configure the following setpoints for the UDC2500 controller.

• A Single Local Setpoint
• 2 Local Setpoints
• a Local Setpoint and a Remote Setpoint

Refer to Subsection 3.11 – Control Set Up Group for configuration details.

Changing the Setpoints

Table 4-9 Procedure for Changing the Local Setpoints

Step

Operation

Press

Result

1

Select the

Setpoint

Lower

Display

Lower

Display

Lower

Display

Until you see:

Upper Display = PV
Lower Display = SP or 2L (Value)

2

Change the

Value

or

To change the Local Setpoint to the value at which you want
the process maintained. The display “blinks” if you attempt
to enter setpoint values beyond the high and low limits..

3

Return to PV

Display

Lower

Display

Lower

Display

Lower

Display

To store immediately or will store after 30 seconds.