Monitoring and Operating the Controller

108

UDC2500 Universal Digital Controller Product Manual

4/07

Step

Operation

Press

Result

5

Initiate Tuning

Select “DoSLOW” or “DoFAST” in
lower display.

6

Tuning in operation

Lower

Display

Lower

Display

Lower

Display

Upper display will flash “TUNE” as
long as ACCUTUNE process is
operating. When process
completes, tuning parameters are
calculated and lower display will
show “NoTune” prompt.

Table 4-15 Procedure for Using MANUAL TUNE for Cool side of Duplex Control

Step

Operation

Press

Result

1

Configure LSP2

Lower

Display

Lower

Display

Lower

Display

Until 2SP (Local Setpoint 2) shows
in the lower display.

2

or

Until LSP2 is a value within the
Cool Zone (output below 50%).

3

Switch to
“Automatic” Mode

M-A

Reset

M-A

Reset

M-A

Reset

Until the “A” indicator is lighted (on
controllers with Manual option).

4

Show Tuning
Prompt

Lower

Display

Lower

Display

Lower

Display

Until “NoTUNE” is shown on lower
display.

5

Initiate Tuning

Select “DoSLOW” or “DoFAST” in
lower display.

6

Tuning in operation

Lower

Display

Lower

Display

Lower

Display

Upper display will flash “TUNE” as
long as ACCUTUNE process is
operating. When process
completes, tuning parameters are
calculated and lower display will
show “NoTune” prompt.