Honeywell UDC2500 User Manual

Page 66

Advertising
background image

Configuration

52

UDC2500 Universal Digital Controller Product Manual

4/07

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

CUR

2

CURRENT SIMPLEX—Type of output using
one 4 mA to 20 mA signal that can be fed
into a positive or negative grounded load of 0
to 1000 ohms. This signal can easily be
configured for 4-20 mA or 0-20 mA operation
via the CRANGE configuration, below.

RLYD

3

TIME DUPLEX—This output algorithm uses
Digital Outputs 1 and 2 for Duplex Time
Proportional Control. The outputs are
updated per the Loop sampling rate
selection. Time Proportional Output has a
resolution of 4.44 msec. Cycle Time is
adjustable from 1 second to 120 seconds.

CURD

4

CURRENT DUPLEX is similar to current
simplex but uses a second current output.
The second output is usually scaled so that
zero and span correspond with 0 % and
50 % output (cool zone). When the output is
0 % to 50 %, the controller uses tuning
parameter set #2, when the output is 50 % to
100 % it uses set #1.

ATTENTION Other prompts affected: 4-20
RNG

CURT

5

CURRENT/TIME DUPLEX is a variation of
duplex with current active for 0 % to 50 %
output (tuning set 2) and time is active 50 %
to 100 % output (tuning set 1).
Relay controls heat, current controls cool.

ATTENTION Other prompts affected: 4-20
RNG

TCUR

6

TIME CURRENT DUPLEX is similar to CUR
TI except that current is active for 50 % to
100 % and time is active for 0 % to 50 %.
Relay controls cool, current controls heat.

ATTENTION Other prompts affected: 4-20
RNG

CRANGE 502

4-20
0-20

0
1

CURRENT OUTPUT RANGE allows the
user to easily select 4-20 mA output or 0-20
mA output operation without the need for
recalibration of the instrument.

OUTRNG 504

CURRENT DUPLEX RANGE ALGORITHM
— Used with Output Algorithm selections
CURD, CURT, or TCUR.