Environmental and Operating Conditions

Parameter Reference Rated Operative

Limits

Transportation and

Storage

Ambient Temperature

25 ± 3 °C
77 ± 5 °F

15 to 55 °C
58 to 131 °F

0 to 55 °C
32 to 131 °F

–40 to 66 °C
–40 to 151 °F

Relative Humidity

10 to 55*

10 to 90*

5 to 90*

5 to 95*

Vibration
Frequency (Hz)
Acceleration (g)


0
0


0 to 70

0.4


0 to 200
0.6


0 to 200

0.5

Mechanical Shock
Acceleration (g)
Duration (ms))


0
0


1

30


5

30


20

30

Line Voltage (Vdc)

+24 ± 1

22 to 27

20 to 27

- -

Line Voltage (Vac)

90 to 240 Vac

24

Vac


120 ± 1
240 ± 2

24 ± 1


90 to 240

20 to 27


90 to 264

20 to 27


- -
- -

- -

Frequency (Hz)
(For

Vac)

50 ± 0.2
60 ± 0.2

49 to 51
59 to 61

48 to 52
58 to 62

- -
- -

* The maximum moisture rating only applies up to 40 °C (104 °F). For higher temperatures, the RH specification is

derated to maintain constant moisture content.