Configuration

4/07

UDC2500 Universal Digital Controller Product Manual

75

Function Prompt

Lower Display

Selection or Range of

Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

AUTO 3

TO AUTO—AUTOMATIC MODE, LAST SP—The
controller will return to the automatic mode and the
last setpoint used before shed.

SHD_SP 1010

LSP

CSP

0

1

SHED SETPOINT RECALL

Note: If SHEDENAB=DISABLE, this prompt will not
be configurable.

TO LSP—Controller will use last local or remote
setpoint used.

TO CSP—When in “slave” mode, the controller will
store the last host computer setpoint and use it at
the Local setpoint. When in “monitor” mode, the
controller will shed to the last UDC Local or
Remote setpoint used, and the LSP is unchanged.

UNITS 1011

PCT
EGR

0
1

PERCENT
ENGINEERING UNITS

CSRATIO 1012

-20.0 to 20.0

COMPUTER SETPOINT RATIO—Computer
setpoint ratio.

CSP_BI 1013 -999 to 9999

COMPUTER SETPOINT RATIO—Computer
setpoint ratio in Engineering Units.

LOOPBK 1014 DIS

ENAB

0
1

LOCAL LOOPBACK tests the communications
hardware.

DISABLE—Disables the Loopback test.

ENABLE—Allows loopback test. The UDC goes
into Loopback mode in which it sends and receives
its own message. The UDC displays PASS or FAIL
status in the upper display and LOOPBACK in the
lower display while the test is running. The UDC
will go into manual mode when LOOPBACK is
enabled with the output at the Failsafe value. The
test will run until the operator disables it here, or
until power is turned off and on.

ATTENTION The instrument does not have to be
connected to the external communications link in
order to perform this test. If it is connected, only
one instrument should run the loopback test at a
time. The host computer should not be transmitting
on the link while the loopback test is active.