Figure 4-3 and draw a ram – Honeywell UDC2500 User Manual

Page 135

Advertising
background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

121

500

400

200

300

°
F

Time/Hours 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

SEG 2

SEG 3

SEG 4

SEG 5

SEG 6

SEG 7

SEG 8

SEG 9

SG 10

SG 11

SG 12

SEG 1

F

20765

Setpoint

Figure 4-3 Ramp/Soak Profile Example

Ramp/Soak Profile Example

Prompt

Function

Segment

Value

Prompt

Function

Segment

Value

STRSEG

Start Seg.

1

SG4 TI

Soak Time

4

1 hr.

ENDSEG End Seg.

12

SG5 RP

Ramp Time

5

1 hr.:30 min.

RP UNIT

Engr. Unit for
Ramp

TIME

SG6 SP

Soak SP

6

250

PG END

Controller
Status

LAST

SP

SG6 TI

Soak Time

6

3 hr.:0 min.

STATE

Controller
State at end

HOLD

SG7 RP

Ramp Time

7

2 hr.:30 min.

TO BEGIN Reset SP

Program

DIS

SG8 SP

Soak SP

8

500

PVSTRT

Program starts

at PV value

DIS

SG8 TI

Soak Time

8

0 hr.:30 min.

RECYCL

Number of
Recycles

2

SG9 RP

Ramp Time

9

0

SOKDEV Deviation

Value

0

SG10 SP

Soak SP

10

400

SG1 RP

Ramp Time

1

1 hr.

SG10 TI

Soak Time

10

0 hr.:30 min.

SG2 SP

Soak SP

2

300

SG11 RP

Ramp Time

11

3 hr.:30 min.

SG2 TI

Soak Time

2

1 hr.:30 min.

SG12 SP

Soak SP

12

200

SG3 RP

Ramp Time

3

1 hr.

SG12TI

Soak Time

12

0 hr.:30 min.

SG4 SP

Soak SP

4

400