Modbus RTU Function Codes

184

UDC2500 Universal Digital Controller Product Manual

4/07

9.3.1 Read Configuration Examples

Example #1

The following is an example of a request to read the Gain 1 value using Function code
20.

Request Message (Read (Gain 1) = ID Tag 001)

02 14 07 06 00 03 00 01 00 02 (CRC16)

Where:
02 =

Address

14

= Function Code 20 (14 hex)

07

= Byte Count

06

= Reference Type

00,03

= File Number (Access Data Value)

00,01 = Register Address (Standard Access Gain 1 - Tag ID #1)

00 02

= Register Count (Floating Point Data)

(CRC16)

This is the response to the above request.

Response Message

02 14 06 05 06 3F C0 00 00 (CRC16)

Where:
02

=

Address

14

= Function Code 20 (14 Hex)

06

= Byte Count

05

= Sub Message Length

06

= Reference Type (IEEE Floating Point)

3F C0 00 00 = 1.50 (Value of Proportional Band)

(CRC16)