2 sp ramp/rate/program – Honeywell UDC2500 User Manual

Page 212

Advertising
background image

Modbus Read, Write and Override Parameters plus Exception Codes

198

UDC2500 Universal Digital Controller Product Manual

4/07

10.7.2 SP

Ramp/Rate/Program

Table 10-10 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Setpoint Ramp/Rate.

Table 10-10 Set-up Group – Setpoint Ramp/Rate

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

SP Ramp

0096 150

INT R/W

0

=

Disabled

1 = Enabled

Single SP Ramp
Time

19

25

FP

R/W

0 to 255 (minutes)

Final Ramp SP
Value

001A

026

FP

R/W

PV Range in Engineering

Units

SP Rate

F0 240

INT

R/W 0

=

Disabled

1 = Enabled

Rate Up (EU/HR) 006C

108

FP

R/W

0 to 9999

Rate Down
(EU/HR)

006D

109

FP

R/W

0 to 9999

Setpoint
Program

00B2 178

INT R/W

0

=

Disabled

1 = Enabled

Start Segment #

58

88

FP

R/W

1 to 12

End Segment
#(Soak)

00B0

176

INT

R/W

0 = Soak 2
1 = Soak 4
2 = Soak 6
3 = Soak 8
4 = Soak 10
5 = Soak 12

Engineering Units
or Ramp
Segments

00B6

182

INT

R/W

0 = HRS:MIN

1 = Degrees/Minute
2 = EU/Hour

Program Recycles 59

89

FP

R/W

0 to 100

Guaranteed Soak
Deviation

0057

087

FP

R/W

0 to 99.9 (0 = no soak)

Program End
State

00B5

181

INT

R/W

0 = Disable SP Program
1 = Hold at Program End