Troubleshooting/Service

4/07

UDC2500 Universal Digital Controller Product Manual

161

7.3 Power-up Tests

What happens at power-up

When power is applied, the controller will run three diagnostic tests. After these tests are
completed, “TEST DONE” is displayed.

Test Failures

If one or more of these tests fail, the controller will go to the Failsafe Manual Mode, and
FAILSF will flash in the lower display and a message indicating which test failed will
appear in the lower display. Then, “DONE” will appear in the lower display.

Three Position Step test failures

For controller configured for Three Position Step Control with motor position indication
and Auto-cal has never been done, the prompt CAL MTR will appear to suggest that the
controller be calibrated.

7.4 Status Tests

Introduction

When required, the results of these tests can be checked to determine the reason the
controller has gone to Failsafe.

How to check the status tests

The procedure in Table 7-2 tells you how to display the results of the status tests.

Table 7-2 Procedure for Displaying the Status Test (Numeric Code 1200)

Results

Step

Operation

Press

Result

1

Select
STATUS
Set Up Group

Setup

Setup

Upper Display

= READ

Lower Display

= STATUS

2

Read the test
results

Function

Function

Function

You will see:

Upper Display

= NO or YES YES indicates a failure

Lower Display

= FAILSAFE

Function

Function

Function

Upper Display

= PASS or FAIL

Lower Display

= TEST