3.15 Display Set Up Group

Introduction

This group includes selections for Decimal place, Units of temperature, Language and
Power frequency.

Function Prompts

Table 3-16 DISPLY Group (Numeric Code 1200) Function Prompts

Function Prompt

Lower Display

Selection or Range of Setting

Upper Display

English

Numeric

Code

English

Numeric

Code

Parameter

Definition

DECMAL 1201 NONE

ONE
TWO

DECIMAL POINT LOCATION—This
selection determines where the decimal point
appears in the display.

NONE—No Decimal Place—fixed, no auto-
ranging 8888
ONE
—1 decimal place 888.8
TWO
—2 decimal places 88.88

ATTENTION Auto-ranging will occur for
selections of one or two decimal places. For
example, should the instrument be
configured for two decimal places and the
PV exceeds 99.99, then the display will
change to a single decimal place so that
values of 100.0 and above can be shown.

UNITS 1202

TEMPERATURE UNITS—This selection will
affect the indication and operation.

F 0

DEG F—Degrees Fahrenheit – Degrees F
Annunciator lighted

C 1

DEG C—Degrees Centigrade – Degrees C
Annunciator lighted

NONE 2

NONE—No temperature annunciators
lighted. Upper and Lower Displays will show
temperature in Degrees Fahrenheit when
inputs are configured for Thermocouple or
RTD types.