Modbus Read, Write and Override Parameters plus Exception Codes

4/07

UDC2500 Universal Digital Controller Product Manual

191

Table 10-1 Control Data Parameters

Parameter

Description

Register
Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Input #1

7B

123

FP

RD

In Engineering Units or
Percentage

Input #2

7C

124

FP

RD

In Engineering Units or
Percentage

PV, SP, Output

7A

122

FP

RD

In Engineering Units or
Percentage

10.3 Read Software Options Status

Read

Doing a Read of register address 00B9 listed in Table 10-2 will tell you which of the
available options are enabled / installed or disabled / not installed.

Table 10-2 Option Status

Parameter

Description

Register
Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Option Status
(Read only)

00B9 185

INT

RD

See Figure 10-1.

The data field in the response message will be a decimal number from 0 to 255. Convert
the decimal number to binary as shown in Figure 10-1.to determine which options are or
are not active.

0 to 255

Convert decimal to binary

0 = not installed

1 = installed

EXAMPLE:

3

Binary

SP Programming –

installed

0

0

0

0

0

1

1

0

Dual Display

installed

SP Programming

0 to 255

Convert decimal to binary

0 = not installed

1 = installed

EXAMPLE:

Binary

SP Programming –

installed

0

0

0

0

0

1

1

0

installed

EXAMPLE:

Binary

SP Programming –

installed

0

0

0

0

0

0

1

1

installed

SP Programming

Dual Display

Limit Controller

Figure 10-1 Software Option Status Information