Monitoring and Operating the Controller

112

UDC2500 Universal Digital Controller Product Manual

4/07

Switch between two sets via keyboard (without automatic switch-over)

Table 4-19 Procedure for Switching PID SETS from the Keyboard

Step

Operation

Press

Result

1

Select Control

Set-up Group

Function

Function

Function

Until you see:
Upper Display
= (the PV value)

Lower Display = PIDS X

(X= 1 or 2)

2

or

To change PID SET 1 to PID SET2 or Vice Versa.

You can use Accutune on each set.

3

Function

Function

Function

To accept changes.

4.14 Alarm Setpoints

Introduction

An alarm consists of a relay contact and an operator interface indication. The alarm relay
is de-energized if setpoint 1 or setpoint 2 is exceeded.

The alarm relay is energized when the monitored value goes into the allowed region by
more than the hysteresis.

The relay contacts can be wired for normally open (NO) energized or normally closed
(NC) de-energized using internal jumper placement. See Table 2-3 in the Section 2 –
Installation for alarm relay contact information.

There are four alarm setpoints, two for each alarm. The type and state (High or Low) is
selected during configuration. See Subsection 3.13 – Configuration for details.

Alarm Setpoints Display

Table 4-20 Procedure for Displaying Alarm Setpoints

Step

Operation

Press

Result

1

Select Alarm

Set-up Group

Setup

Setup

Until you see:
Upper Display
= SET

Lower Display = ALARMS

2

Access the Alarm

Setpoint Values

Function

Function

Function

To successively display the alarm setpoints and their values.
Their order of appearance is shown below.
Upper Display = (the alarm setpoint value)
Range values are within the range of the selected
parameters except:
DEVIATION (DE) value = PV Span
EVENTS (E-ON/E-OF) value = Event Segment Number
PV RATE OF CHANGE (PVRT) = The amount of PV
change in one minute in engineering units.
LOOP BREAK ALARMS (BRAK) = The timer value may be
changed only for controllers configured for ON/OF.