Installation

26

UDC2500 Universal Digital Controller Product Manual

4/07

Alarm
Relay#1

L1

L2/N

4

5

7

8

9

N.C.

N.O.

Time Simplex

2

3

Alarm #2 is not available with Time Proportional Duplex or Three Position Step Control unless the Dual Relay option is used.

Electromechanical relays are rated at 5 Amps @ 120 Vac or 240 Vac or 30 Vdc.
Customer should size fuses accordingly. Use Fast Blo fuses only.

19

20

21

22

23

24

25

26

27

Time Duplex

Alarm
Relay#2

N.C.

N.O.

6

Alarm
Relay#1

L1

L2/N

4

5

7

8

9

N.C.

N.O.

19

20

21

22

23

24

25

26

27

6

To terminal

7 or 9

Relay Load

3

Load

Supply
Power

+

+

Output #1

1

+

Customer Supplied
Electromechanical relay

Customer Supplied
Solid-State relay

+

+

Output #1

1

+

Customer Supplied
Electromechanical relay

Customer Supplied
Solid-State relay

+

+

Output #2

1

+

Customer Supplied
Electromechanical relay

Customer Supplied
Solid-State relay

CAUTION

Open collector outputs are internally powered at +30 Vdc. Connecting an external
power supply will damage the controller.

1

2

To terminal

4 or 6

Relay Load

To terminal

7 or 9

Relay Load

3

3

Load

Supply
Power

Load

Supply
Power

Figure 2-10 Open Collector Output

See Table 2-6 for relay terminal connections for other Output Algorithm Types.