Input Calibration

150

UDC2500 Universal Digital Controller Product Manual

4/07

Step

Operation

Press

Result

or

until you change the input selection in the upper display back to the
proper selection. You will see:

Upper Display

= Original Input Selection that matches your

type of sensor.
Lower Display

= INxTYP

4

Return to Normal
Operation

Lower

Display

Lower

Display

Lower

Display

to return to Normal operating mode.

The factory calibration will be restored. If the problem is not
corrected, contact the Honeywell Technical Assistance Center at 1-
800-423-9883 USA and Canada