7 start up procedure for operation, Table 4-6 procedure for starting up the controller – Honeywell UDC2500 User Manual

Page 113

Advertising
background image

Monitoring and Operating the Controller

4/07

UDC2500 Universal Digital Controller Product Manual

99

4.7 Start Up Procedure for Operation

Table 4-6 Procedure for Starting Up the Controller

Single

Display

Step

Dual

Display

Step

Operation

Press

Result

1 1 Configure

controller

Setup

Setup

Make sure the controller has been configured properly
and that all the values and selections have been recorded
on the Configuration Record Sheet. See steps 4 & 5.

2

Select
Manual
Mode

M-A

Reset

M-A

Reset

M-A

Reset

N/A for Single Display Model

Until “M” indicator is ON.
The controller is in manual mode.

3

Adjust

the

Output

or

N/A for Single Display Model

To adjust the output value and ensure that the final control
element is functioning correctly.

Upper Display = PV Value

Lower Display = OT and the output value in %

4

Select
Automatic
Mode

M-A

Reset

M-A

Reset

M-A

Reset

N/A for Single Display Model

Until “A” indicator is ON.

The controller is in Automatic mode.

The controller will automatically adjust the output to
maintain the process variable at setpoint.

2 5 Enter

the

Local
Setpoint

Lower

Display

Lower

Display

Lower

Display

Upper Display = Pv Value

Lower Display = SP and the Local Setpoint Value

or

To adjust the local setpoint to the value at which you want
the process variable maintained.

The local setpoint cannot be changed if the Setpoint
Ramp function is running.

3 6 Tune

the

Controller

Setup

Setup

Use Accutune to tune the controller; see product manual
for detailed procedure or refer to Tuning Set Up group to
set that the selections for PB or GAIN, RATE T, and I MIN
or I RPM.