Modbus Read, Write and Override Parameters plus Exception Codes

212

UDC2500 Universal Digital Controller Product Manual

4/07

Parameter

Description

Register

Address

Data

Type

Access

Data Range or

Enumerated Selection

Hex

Decimal

Digital Input
#1

00BA 186

INT R/W

0 = None
1 = To Manual
2 = To Local Setpoint #1
3 = To Local Setpoint #2
4 = To Direct Action
5 = To Hold Ramp
6 = To PID Set #2
7 = To Run Ramp
8 = To Begin
9 = No I (Reset)
10 = To Manual Failsafe

Output

11 = Disable Keyboard
12 = To Timer
13 = Initiate Limit Cycle

Tuning

14 = Setpoint Initialization

(SP=PV)

15 = To RSP
16 = Manual Latching
17 = Output 1 tracks Input 2
18 = Start/Restart SP Ramp or

SP Program

Digital Input
#1
Combinations

00BC 188

INT R/W

0 = Disable
1 = +PID2
2 = +Direct
3 = +LSP2
4 = +LSP1
5 = +Run

Digital Input
#2 *

00BB

187

INT

R/W

Same as Digital Input #1

Digital Input
#2
Combinations
*

00BD 189

INT R/W

Same as Digital Input #1

Combinations

* Auxiliary Output and Digital Input #2 are mutually exclusive.