Honeywell UDC2500 User Manual

Page 180

Advertising
background image

Troubleshooting/Service

166

UDC2500 Universal Digital Controller Product Manual

4/07

Procedure #1

Table 7-5 explains how to troubleshoot power failure symptoms.

Table 7-5 Troubleshooting Power Failure Symptoms

Step

What to do

How to do it

1

Check the AC line voltage.

Use a voltmeter to measure the AC voltage
across terminals L1 and L2 on the rear
terminal panel of the controller.

Check the earth ground connection.

2

Make sure the chassis plugs
into the rear of the case
properly.

Withdraw the chassis and visually inspect the
controller board and the inside of the case.

3

Check the system for Brown-
outs, heavy load switching, etc.,
and conformance to installation
instructions.

Refer to Section 2 - Installation.

4

Change Power board.

Installation instructions supplied with new
board.

Procedure #2

Table 7-6 explains how to troubleshoot Current Output failure symptoms.

Table 7-6 Troubleshooting Current Output Failure

Step

What to do

How to do it

1

Make sure the controller is
configured for Current output
and the proper range (4 to 20 or
0 to 20) is configured.

Make Output Set Up group function prompt
OUT ALG = CUR.

Make the Output Set UP group function
prompt CRANGE = 4–20 or 0–20 per your
application.

Refer to Section 3 - Configuration.

2

Check the field wiring.

Output impedance must be less than or equal
to 1000 ohms.

3

Check the output.

Put the controller into Manual mode and
change the output from 0 % to 100 % (4-20
mA). Use a DC milliammeter at the rear
terminals to verify the output.

4

Recalibrate the Current
Proportional output.

Refer to Section 6 - Output Calibration for
details.

5

Change Current Output board.

Installation instructions provided with new
board.

6

Change Controller

Advertising