Installation

8

UDC2500 Universal Digital Controller Product Manual

4/07

Pre-installation Information

If the controller has not been removed from its shipping carton, inspect the carton for
damage then remove the controller.

• Inspect the unit for any obvious shipping damage and report any damage due to

transit to the carrier.

• Make sure a bag containing mounting hardware is included in the carton with the

controller.

• Check that the model number shown on the inside of the case agrees with what you

have ordered.

2.2 Condensed Specifications

Honeywell recommends that you review and adhere to the operating limits listed in Table
2-1 when you install your controller.

Table 2-1 Condensed Specifications

Specifications

Analog Inputs

Accuracy:

± 0.25% of full scale typical (± 1 digit for display)
Can be field calibrated to ± 0.05% of full scale typical
16-bit resolution typical

Sampling Rate: Both inputs are sampled six times per second

Temperature Stability: ± 0.01% of Full Scale span / ˚C change—typical

Input Impedance:

4-20 Milliampere Input: 250 ohms
0-10 Volt Input: 200K ohms
All Others: 10 megohms

Maximum Lead Wire Resistance:

Thermocouples: 50 ohms/leg
100 ohm, 200 ohm and 500 ohm RTD: 100 ohms/leg
100 ohm Low RTD: 10 ohms/leg

Analog Input Signal
Failure Operation

Burnout Selections: Upscale, Downscale, Failsafe or None
Thermocouple Health: Good, Failing, Failure Imminent or Failed
Failsafe Output Level: Configurable 0-100% of Output range

Stray Rejection

Common Mode
AC (50 or 60 Hz): 120 dB (with maximum source impedance of 100 ohms) or ± 1 LSB (least
significant bit) whichever is greater with line voltage applied.
DC: 120 dB (with maximum source impedance of 100 ohms) or a ±1 LSB whichever is
greater with 120 Vdc applied.
DC (to 1 KHz): 80 dB (with maximum source of impedance of 100 ohms) or ±1 LSB
whichever is greater with 50 Vac applied.

Normal Mode
AC (50 or 60 Hz): 60 dB (with 100 % span peak-to-peak maximum)

Digital Inputs (Two)
(Optional)

+30 Vdc source for external dry contacts or isolated solid state contacts. Digital Inputs are
isolated from line power, earth ground, analog inputs and all outputs except for the Second
Current Output.

The second Digital Input is mutually exclusive with the Second Current Output.