4 control and alarm relay contact information – Honeywell UDC2500 User Manual

Page 28

Advertising
background image

Installation

14

UDC2500 Universal Digital Controller Product Manual

4/07

2.4 Control and Alarm Relay Contact Information

Control Relays

ATTENTION

Control relays operate in the standard control mode (that is, energized when output state is on).

Table 2-2 Control Relay Contact Information

Unit Power

Control Relay

Wiring

Control Relay

Contact

Output #1 or #2

Indicator Status

N.O. Open

Off

N.C. Closed

Off

Open

Off

N.O.

Closed

On

Closed

Off

On

N.C.

Open

On

Alarm Relays

ATTENTION

Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm
sate). This results in alarm actuation when power is OFF or when initially applied, until the unit
completes self diagnostics. If power is lost to the unit, the alarms will de-energize and thus the
alarm contacts will close.

Table 2-3 Alarm Relay Contact Information

Variable NOT in Alarm State

Variable in Alarm State

Unit

Power

Alarm Relay

Wiring

Relay

Contact

Indicators

Relay

Contact

Indicators

N.O. Open

Open

Off

N.C. Closed

Off

Closed

Off

N.O. Closed

Open

On

N.C.

Open

Off

Closed

On